Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
221 | 443
bit 118
000B: Master speed
0001B: 1
st
step speed frequency
0010B: 2
nd
step speed frequency
0011B: 3
rd
step speed frequency
0100B: 4
th
step speed frequency
0101B: 5
th
step speed frequency
0110B: 6
th
step speed frequency
0111B: 7
th
step speed frequency
1000B: 8
th
step speed frequency
1001B: 9
th
step speed frequency
1010B: 10
th
step speed frequency
1011B: 11
th
step speed frequency
1100B: 12
th
step speed frequency
1101B: 13
th
step speed frequency
1110B: 14
th
step speed frequency
1111B: 15
th
step speed frequency
bit 12
1: Enable bit 0611 function
bit 1413
00B: No function
01B: Operated by the digital keypad
10B: Operated by Pr.00-21 setting
11B: Change the operation source
bit 15
Reserved
2001H
Frequency command (XXX.XX Hz)
2002H
bit 0
1: E.F. (External Fault) ON
bit 1
1: Reset command
bit 2
1: B.B. ON
bit 43
Reserved
bit 5
1: Enable fire mode
bit 156
Reserved
Status monitor read only
2100H
High byte: Warning code / Low Byte: Error code
2101H
bit 10
AC motor drive operation status
00B: The drive stops
01B: The drive is decelerating
10B: The drive is in standby status
11B: The drive is operating
bit 2
1: JOG command
bit 43
Operation direction
00B: FWD running
01B: From REV running to FWD running
10B: From FWD running to REV running