11B: REV running
bit 8
1: Master frequency controlled by the communication interface
bit 9
1: Master frequency controlled by the analog / external terminal signal
bit 10
1: Operation command controlled by the communication interface
bit 11
1: Parameter locked
bit 12
1: Enable to copy parameters from keypad
bit 1513
Reserved
2102H
Frequency command (XXX.XX Hz)
2103H
Output frequency (XXX.XX Hz)
2104H
Display the drive’s output current (XX.XX A). When the current is higher than 655.35,
it automatically shifts one decimal place as (XXX.X A). See the high byte of 211F for
information on the decimal places.
2105H
DC bus voltage (XXX.X V)
2106H
Output voltage (XXX.X V)
2107H
Current step for the multi-step speed operation
2108H
Reserved
2109H
Counter value
210AH
Output power factor angle (XXX.X)
210BH
Output torque (XXX.X %)
210CH
Actual motor speed (XXXXX rpm)
210DH
Reserved
210EH
Reserved
210FH
Power output (X.XXX kW)
2116H
Multi-function display (Pr.00-04)
211BH
Maximum Operation Frequency (Pr.01-00) or Maximum User-defined Value (Pr.00-
26)
When Pr.00-26 is 0, this value is equal to Pr.01-00 setting
When Pr.00-26 is not 0, and the command source is keypad, this value = Pr.00-24 *
Pr.00-26 / Pr.01-00.
When Pr.00-26 is not 0, and the command source is 485, this value = Pr.09-10 *
Pr.00-26 / Pr.01-00.
211FH
High byte: the decimal place of current value (display)
2200H
Display the drive’s output current (XX.XX A). When the current is higher than 655.35,
it automatically shifts one decimal place as (XXX.X A). Refer to the high byte of 211F
for information on the decimal places.
2201H
Counter value
2202H
Actual output frequency (XXXXX Hz)
2203H
DC bus voltage (XXX.X V)
2204H
Output voltage (XXX.X V)
2205H
Power factor angle (XXX.X)
2206H
Display the output power of U, V, W (XXXX.X kW)
2207H
Display the motor speed estimated by the drive or encoder feedback (XXXXX rpm)