Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
226 | 443
Pr.
Explanation
Settings
Default
09-30
Communication decoding method
0: Decoding method 1
1: Decoding method 2
1
Decoding Method 1
Decoding Method 2
Source of
Operation
Control
Digital Keypad
Digital keypad controls the drive action regardless of decoding method 1 or 2.
External Terminal
External terminal controls the drive action regardless of decoding method 1 or 2.
RS-485
See address: 2000h20FFh
See address: 6000h60FFh
CANo
pen
See index: 2020-01h2020-FFh
See index:2060-01h2060-FFh
Communication Card
See address: 2000h20FFh
See address: 6000h60FFh
PLC
PLC command controls the drive action regardless of decoding method 1 or 2.
Pr.
Explanation
Settings
Default
09-33
PLC command force to 0
0 to 65535
0
bit
Description
bit 0
Before PLC scan, set the PLC target frequency = 0
bit 1
Before PLC scan, set the PLC target torque = 0
bit 2
Before PLC scan, set the speed limit of torque mode = 0
Pr.
Explanation
Settings
Default
09-35
PLC address
1 to 254
2
09-36
CANopen slave address
0: Disable
1 to 127
0
09-37
CANopen speed
0: 1 Mbps
1: 500 Kbps
2: 250 Kbps
3: 125 Kbps
4: 100 Kbps
5: 50 Kbps
0
09-39
CANopen warning record
bit 0: CANopen software disconnection 1
(CANopen guarding time-out)
bit 1: CANopen software disconnection 2
(CANopen heartbeat time-out)
bit 3: CANopen SDO time-out
bit 4: CANopen SDO buffer overflow
bit 5: CANopen hardware disconnection warning
0