Descriptions of Parameter Settings
Descriptions of Parameter Settings
230 | 443
Fig. 110:
Pr.
Explanation
Settings
Default
10-10
Encoder stall level
0: No function
0 to 120%
115
Determines the maximum encoder feedback signal allowed before a fault occurs; the maximum operation
frequency Pr.01-00 = 100%.
Pr.
Explanation
Settings
Default
10-11
Detection time of encoder stall
0.0 to 2.0 sec.
0.1
10-12
Encoder stall action
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
2
When the drive output frequency exceeds the encoder stall level (Pr.10-10), the drive starts to count the time.
When the error time exceeds the encoder stall detection time (Pr.10-11), the drive implements the encoder stall
action.
Pr.
Explanation
Settings
Default
10-13
Encoder slip range
0: Disable
0 to 50%
50
10-14
Detection time of encoder slip
0.0 to 10.0 sec.
0.5
10-15
Encoder stall and slip error action
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
2
● This parameter acts on the settings for Pr.10-13–Pr.10-15:
● When the value of (rotation speed – motor frequency) exceeds the Pr.10-13 setting, and the detection time
exceeds Pr.10-14; the drive starts to count the time. If the detection time exceeds Pr.10-14, the encoder
feedback signal error occurs.