Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
235 | 443
Pr.
Explanation
Settings
Default
10-53
Angle detection method
0: Disabled
1: Force attracting the rotor to zero degrees
2: High frequency injection
3: Pulse injection
0
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
11-00
System control
bit 0: Auto-tuning for ASR and APR
bit 3: Dead time compensation closed
bit 7: Save or do not save the frequency
0
Pr.
Explanation
Settings
Default
11-01
Per-unit of system inertia
1 to 65535 (256 = 1 PU)
256