Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
239 | 443
Fig. 113:
All control modes are based on 100% of the motor rated current except:
IM: VF, VFPG, SVC
PM: PMSVC
Pr.
Explanation
Settings
Default
11-21
Flux weakening curve for motor 1
gain value
0 to 200%
90
11-22
Flux weakening curve for motor 2
gain value
0 to 200%
90
Adjusts the output voltage for the flux weakening curve.
For the spindle application, use this adjustment method:
● Run the motor to the highest frequency.
● Observe the output voltage.
● Adjust the Pr.11-21 (motor 1) or Pr.11-22 (motor 2) setting to make the output voltage reach the motor rated
voltage.