Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
240 | 443
Pr.
Explanation
Settings
Default
11-23
Flux weakening area speed
response
0 to 150%
65
Controls the speed in the flux weakening area. The larger the value, the faster the acceleration/deceleration. In
normal condition, you do not need to adjust this parameter.
Pr.
Explanation
Settings
Default
11-27
Maximum torque command
0 to 500%
100
Determines the upper limit of the torque command (motor rated torque is 100%).
Calculation equation for the motor rated torque:
Motor rated torque: ;
P (W) value = Pr.05-02; ω (rad / s) value = Pr.05-03;
Pr.
Explanation
Settings
Default
11-28
Torque offset source
0: Disable
1: Analog signal input
2: RS-485 communication (Pr.11-29)
3: Controlled through external terminals (Pr.11-30–11-32)
0
Fig. 114: Specifies the torque offset source.
When set to 3, the torque offset sources are Pr.11-30, Pr.11-31 or Pr.11-32 according to the multi-function input
terminal settings 31, 32 or 33.
Normally open (N.O.) contact: ON = contact closed, OFF = contact open
)/(
)(
).(
srad
WP
MNT
=
srad
RPM
/
60
2
=
srad
RPM
/
60
2
=