Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
245 | 443
00-20
Master frequency command source
(AUTO, REMOTE)
2 (External analog input)
00-21
Operation command source
(AUTO, REMOTE)
1 (External terminals)
00-22
Stop method
0 (Ramp to stop)
00-23
Motor direction control
1 (Disable reverse)
01-00
Maximum operation frequency
Default setting
01-01
Output frequency of motor 1
(Base frequency / Motor’s rated frequency)
Default setting
01-02
Output voltage of motor 1
(Base voltage / Motor’s rated voltage)
Default setting
01-03
Mid-point frequency 1 of motor 1
Default setting
01-04
Mid-point voltage 1 of motor 1
Default setting
01-05
Mid-point frequency 2 of motor 1
Default setting
01-06
Mid-point voltage 2 of motor 1
Default setting
01-07
Minimum output frequency of motor 1
Default setting
01-08
Minimum output voltage of motor 1
Default setting
01-11
Output frequency lower limit
20 (Hz)
01-12
Acceleration time 1
20 (sec.)
01-13
Deceleration time 1
20 (sec.)
03-00
Analog input selection (AVI)
0 (No function)
03-01
Analog input selection (ACI)
1 (Frequency command)
05-01
Full-load current for induction motor 1 (A)
Default setting
05-03
Rated speed for induction motor 1 (rpm)
Default setting
05-04
Number of poles for induction motor 1
Default setting
Setting 03: Fan
The following table lists the relevant fan setting application parameters.
Pr.
Parameter Name
Settings
00-11
Speed control mode
0 (IMVF)
00-16
Load selection
0 (Normal load)
00-17
Carrier frequency
Default setting
00-20
Master frequency command source
(AUTO, REMOTE)
2 (External analog input)
00-21
Operation command source
(AUTO, REMOTE)
1 (External terminals)
00-22
Stop method
1 (Coast to stop)
00-23
Motor direction control
1 (Disable reverse)
00-30
Master frequency command source
(HAND, LOCAL)
0 (Digital keypad)
00-31
Operation command source
(HAND, LOCAL)
0 (Digital keypad)