Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
246 | 443
01-00
Maximum operation frequency
Default setting
01-01
Output frequency of motor 1
(Base frequency / Motor’s rated frequency)
Default setting
01-02
Output voltage of motor 1
(Base voltage / Motor’s rated voltage)
Default setting
01-03
Mid-point frequency 1 of motor 1
Default setting
01-04
Mid-point voltage 1 of motor 1
Default setting
01-05
Mid-point frequency 2 of motor 1
Default setting
01-06
Mid-point voltage 2 of motor 1
Default setting
01-07
Minimum output frequency of motor 1
Default setting
01-08
Minimum output voltage of motor 1
Default setting
01-10
Output frequency upper limit
50 (Hz)
01-11
Output frequency lower limit
35 (Hz)
01-12
Acceleration time 1
15 (sec.)
01-13
Deceleration time 1
15 (sec.)
01-43
V/F curve selection
2 (V/F curve to the power of 2)
02-05
Multi-function input command 5 (MI5)
16 (Rotating speed command from ACI)
02-16
Multi-function output 2 (MO1)
11 (Malfunction indication)
02-17
Multi-function output 3 (MO2)
1 (Indication during RUN)
03-00
Analog input selection (AVI)
1 (Frequency command)
03-01
Analog input selection (ACI)
1 (Frequency command)
03-28
AVI terminal input selection
0 (010 V)
03-29
ACI terminal input selection
1 (010 V)
03-31
AFM output selection
0 (010 V)
03-50
Analog input curve selection
1 (three-point curve of AVI)
07-06
Restart after momentary power loss
2 (Speed tracking by the minimum output freqeuncy)
07-11
Number of times of restart after fault
5 (times)
07-33
Auto-restart interval of fault
60 (sec.)
Pr.
Parameter Name
Settings
00-11
Speed control mode
0 (IMVF)
00-16
Load selection
0 (Normal load)
00-20
Master frequency command source
(AUTO, REMOTE)
2 (External analog input)
00-21
Operation command source
(AUTO, REMOTE)
1 (External terminals)
00-23
Motor direction control
1 (Disable reverse)
01-00
Maximum operation frequency
Default setting