142: Auto-tune error 1 (DC test stage) (AuE1)
143: Auto-tune error 2 (High frequency test stage) (AuE2)
144: Auto-tune error 3 (Rotary test stage) (AuE3)
● The parameters record when the fault occurs and forces a stop.
● When low voltage at stop fault (LvS) occurs, the fault is not recorded. When low-voltage during operation faults
(LvA, Lvd, Lvn) occur, the faults are recorded.
● When the dEb function is valid and enabled, the drive executes dEb and records fault code 62 to Pr.06-17–06-
22 and Pr.14-70–14-73 simultaneously.
Pr.
Explanation
Settings
Default
14-74
Over-torque detection selection
(motor 3)
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0
14-77
Over-torque detection selection
(motor 4)
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0
● When you set Pr.14-74 and Pr.14-77 to 1 or 3, a warning message displays but there is no error record.
● When you set Pr.14-74 and Pr.14-77 to 2 or 4, an error message displays and there is an error record.
Pr.
Explanation
Settings
Default
14-75
Over-torque detection level (motor
3)
10 to 250%
(100% corresponds to the rated current of the drive)
120
14-78
Over-torque detection level (motor
4)
10 to 250%
(100% corresponds the rated current of the drive)
120
14-76
Over-torque detection time (motor
3)
0.1 to 60.0 sec.
0.1
14-79
Over-torque detection time (motor
4)
0.1 to 60.0 sec.
0.1
● When the output current exceeds the over-torque detection level (Pr.14-75 or Pr.14-78) and exceeds the over-
torque detection time (Pr.14-76 or Pr.14-79), the over-torque detection follows the setting of Pr.14-74 or Pr.14-
77.
● When you set Pr.14-74 or Pr.14-77 to 1 or 3, an ot3/ot4 warning displays while the drive keeps running after
over-torque detection. The warning remains on until the output current is smaller than 5% of the over-torque
detection level.