Operating Instructions

Fault Codes
Digital Keypad
311 | 443
Record
Yes
Cause
Corrective Actions
Power-off
Improve power supply condition.
Power voltage changes
Adjust voltage to the power range of the drive.
Start up the motor with large capacity
Check the power system.
Increase the capacity of power equipment.
Sudden load
Reduce the load.
Increase the drive capacity.
DC bus
Install DC reactor(s).
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
13
Low-voltage at constant
speed (Lvn)
DC bus voltage is lower than Pr.06-00 setting value at constant
speed
Action and Reset
Action level
Pr.06-00 (Default = depending on the model)
Action time
Immediately act when the DC bus voltage is lower than Pr.06-00
Fault treatment parameter
NA
Reset method
Manual reset
Reset condition
Reset when the DC bus voltage is higher than Pr.06-00 + 30V
Record
Yes
Cause
Corrective Actions
Power-off
Improve power supply condition.
Power voltage changes
Adjust voltage to the power range of the drive
Start up the motor with large capacity
Check the power system.
Increase the capacity of power equipment.
Sudden load
Reduce the load.
Increase the drive capacity.
DC bus
Install DC reactor(s).
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
14
Low-voltage at stop (LvS)
DC bus voltage is lower than Pr.06-00 setting value at stop
Hardware failure in voltage detection
Action and Reset
Action level
Pr.06-00 (Default = depending on the model)
Action time
Immediately act when the DC bus voltage is lower than Pr.06-00
Fault treatment parameter
N/A
Reset method
Manual / Auto:
230V series: Lv level + 30 Vdc + 500 ms
460V series: Lv level + 60 Vdc + 500 ms
575V series: Lv level + 75 Vdc + 500 ms
Reset condition
500 ms