cables are short, CbFE fault occurs.
Action level
Immediately act
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
Cycle the power
Record
Yes
Cause
Corrective Actions
Check if the CANopen card is installed
Ensure the CANopen card is installed.
Check if the CANopen speed
is correct
Reset CANopen speed (Pr.09-37)
Malfunction caused by interference
Verify the wiring and grounding of the communication circuit.
Separate the communication circuit from the main circuit, or wire in 90 degree for effective
anti-interference performance.
Ensure the communication circuit is wired in series.
Use CANopen cable or add terminating resistance.
Communication cable is broken or bad
connected
Check or replace the communication cable.
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
105
CANopen index error
(CidE)
CANopen index error
Action and Reset
Action level
Software detection
Action time
Immediately act
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
The upper unit sends a reset package to clear this fault
Record
Yes
Cause
Corrective Actions
Incorrect setting of CANopen index
Reset CANopen Index (Pr.00-02=7)
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
106
CANopen station address
error (CAdE)
CANopen station address error (only supports 1127)
Action and Reset
Action level
Software detection
Action time
Immediately act
Fault treatment parameter
N/A
Reset method
Manual reset (Pr.00-02=7)