Operating Instructions

Fault Codes
Digital Keypad
343 | 443
Reset condition
N/A
Record
Yes
Cause
Corrective Actions
Incorrect setting of CANopen station
address
Disable CANopen (Pr.09-36=0)
Reset CANopen (Pr.00-02=7)
Reset CANopen station address (Pr.09-36)
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
107
CANopen index setting
exceed limit (CFrE)
CANopen memory error
Action and Reset
Action level
When you update the firmware version of the control board, the FRAM internal data does not
change, then CFrE fault occurs.
Action time
Immediately act
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
Pr.00-02=7
Record
Pr.00-21=3, the fault is recorded
Cause
Corrective Actions
CANopen internal memory error
Disable CANopen (Pr.09-36=0)
Reset CANopen (Pr.00-02=7)
Reset CANopen station address (Pr.09-36)
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
111
InrCOM time-out error (ictE)
Internal communication overtime error
Action and Reset
Action level
Pr.09-31=-1 -10 (there is no -9), when the internal communication between Slave and Master is
abnormal, ictE fault occurs.
Action time
Immediately act
Fault treatment parameter
N/A
Reset method
Automatically reset after the internal communication is normal
Reset condition
N/A
Record
Yes