Operating Instructions
Summary of Parameter Settings
00 Drive Parameters
35 | 443
Pr.
Explanation
Settings
Default
00-21
Operation command source
(AUTO, REMOTE)
Note: HOA (Hand-Off-Auto)
function is valid only when you
use with MO function setting 42
and 56 or with KPC-CC01
(optional).
0: Digital keypad
1: External terminals
2: RS-485 communication input
3: CANopen communication card
5: Communication card (does not include CANopen card)
0
00-22
Stop method
0: Ramp to stop
1: Coast to stop
0
00-23
Motor direction control
0: Enable forward/reverse
1: Disable reverse
2: Disable forward
0
00-24
Digital operator (keypad)
frequency command memory
Read only
Read only
00-25
User-defined characteristics
bit 0–3: user-defined decimal places
● 0000h-0000b: no decimal place
● 0001h-0001b: one decimal place
● 0002h-0010b: two decimal places
● 0003h-0011b: three decimal places
bit 4–5: user-defined unit
● 000xh: Hz
● 001xh: rpm
● 002xh: %
● 003xh: kg
● 004xh: m/s
● 005xh: kW
● 006xh: HP
● 007xh: ppm
● 008xh: 1/m
● 009xh: kg/s
● 00Axh: kg/m
● 00Bxh: kg/h
● 00Cxh: lb/s
● 00Dxh: lb/m
● 00Exh: lb/h
● 00Fxh: ft/s
● 010xh: ft/m
● 011xh: m
● 012xh: ft
● 013xh: degC
● 014xh: degF
● 015xh: mbar
● 016xh: bar
● 017xh: Pa
● 018xh: kPa
● 019xh: mWG
● 01Axh: inWG
● 01Bxh: ftWG
0