Operating Instructions
Summary of Parameter Settings
01 Basic Parameters
37 | 443
Pr.
Explanation
Settings
Default
4: External UP / DOWN key input (multi-function input terminals)
5: Pulse input without direction command (See Pr.10-16)
6: Not supported
7: Digital keypad potentiometer knob
8: Not supported
00-36
Master and auxiliary frequency
command selection
0: Master + auxiliary frequency
1: Master - auxiliary frequency
2: Auxiliary - master frequency
0
00-47
Output phase order selection
0: Standard
1: Exchange the rotation direction
0
00-48
Display filter time (current)
0.001–65.535 sec.
0.100
00-49
Display filter time (keypad)
0.001–65.535 sec.
0.100
00-50
Software version (date)
Read only
Read only
01 Basic Parameters
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
01-00
Maximum operation frequency
0.00–599.00 Hz
60.00 / 50.00
01-01
Output frequency of motor 1
(Base frequency/Motor’s rated
frequency)
0.00–599.00 Hz
60.00 / 50.00
01-02
Output voltage of motor 1
(Base voltage/Motor’s rated
voltage)
115V/230V models: 0.0–255.0V
460V models: 0.0–510.0V
575V models: 0.0–637.0V
220.0
440.0
575.0
01-03
Mid-point frequency 1 of motor 1
0.00–599.00 Hz
3.00
01-04
Mid-point voltage 1 of motor 1
115V/230V models: 0.0–240.0V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
11.0
22.0
40.0
01-05
Mid-point frequency 2 of motor 1
0.00–599.00 Hz
1.50
01-06
Mid-point voltage 2 of motor 1
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
5.0
10.0
26.1
01-07
Minimum output frequency of
motor 1
0.00–599.00 Hz
0.50
01-08
Minimum output voltage of motor
1
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
1.0
2.0
16.7
01-09
Start-up frequency
0.00–599.00 Hz
0.50
01-10
Output frequency upper limit
0.00–599.00 Hz
599.00