Operating Instructions

Safe Torque Off Function
Test and Fault Confirmation
386 | 443
ID No.
KPMS-LE01
Keypad Display
Descriptions
72
STO1SCM1 internal loop detection error
Cause and Corrective Actions
STO1 and SCM1 short circuit lines are not connected
1. Re-connect the short circuit line.
Hardware failure
1. After you make sure all the wiring is correct, if STL1 fault still exists after cycling the power, return to
the factory for repair.
76
Safe Torque Off function active
Cause and Corrective Actions
The switch action of STO1/SCM1 and STO2/SCM2 (OPEN)
1. Reset the switch (ON) and cycle the power.
77
STO2SCM2 internal loop detection error.
Cause and Corrective Actions
STO2 and SCM2 short circuit lines are not connected
1. Re-connect the short circuit line.
Hardware failure
1. After you make sure all the wiring is correct, if STL2 fault still exists after cycling the power, return to
the factory for repair.
78
STO1SCM1 and STO2SCM2 internal loop detection error.
Cause and Corrective Actions
STO1 and SCM1, or STO2 and SCM2 short circuit lines are not connected
1. Re-connect the short circuit line.
Hardware failure
1. After you make sure all the wiring is correct, if STL3 fault still exists after cycling the power, return to
the factory for repair.