Operating Instructions
Optional Accessories
Magnetic Contactor/Air Circuit Breaker and Non-fuse Circuit Breaker
392 | 443
Magnetic Contactor/Air Circuit Breaker and Non-fuse Circuit
Breaker
Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be ≥ 140°F (60°C) and for ACB ≥ 122°F (50°C).
Consider temperature derating for components with ON /OFF switch in accordance with the ambient temperature of
the on-site distribution panel.
Frame
Model
Heavy Duty
Output Current [A]
Heavy Duty
Input Current [A]
MC/ACB Selection
[A]
A
RT0002-11N
6
1.6
11
RT0005-11N
9.4
2.5
18
C
RT001X-11N
18
4.8
32
Table 19: 115V Models
Frame
Model
Heavy Duty
Output Current [A]
Heavy Duty
Input Current [A]
MC/ACB Selection
[A]
A
RT0002-21N
5.1
1.6
9
RT0005-21N
7.3
2.8
13
RT0002-23N
1.9
1.6
9
RT0005-23N
3.4
2.8
9
RT001X-23N
5.8
4.8
11
B
RT0002-21F
5.1
1.6
9
RT0005-21F
7.3
2.8
13
RT001X-21F
10.8
4.8
18
RT001X-21N
10.8
4.8
18