Summary of Parameter Settings
03 Analog Input/Output Parameters
46 | 443
Pr.
Explanation
Settings
Default
03-11
Analog input gain (AVI)
-500.0–500.0%
100.0
03-12
Analog input gain (ACI)
-500.0–500.0%
100.0
03-15
Analog input filter time (AVI)
0.00–20.00 sec.
0.01
03-16
Analog input filter time (ACI)
0.00–20.00 sec.
0.01
03-18
Analog input addition function
0: Disable (AVI, ACI)
1: Enable (excludes analog extension card)
0
03-19
Signal loss selection for analog
input 4 to 20 mA
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display ACE
0
03-20
Multi-function output (AFM)
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
12: Iq current command
13: Iq feedback value
14: Id current command
15: Id feedback value
16: Vq-axis voltage command
17: Vd-axis voltage command
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
0
03-21
Analog output gain (AFM)
0.0 to 500.0%
100.0
03-22
Analog output in REV direction
(AFM)
0: Absolute value in output voltage
1: Reverse output 0V; forward output 0 to 10V
2: Reverse output 5 to 0V; forward output 5 to 10V
0
03-27
AFM output bias
-100.00 to 100.00%
0.00
03-28
AVI terminal input selection
0: 0 to 10V (Pr.03-63–Pr.03-68 is valid)
3: -10 to 10V (Pr.03-69–Pr.03-74 are valid)
0
03-29
ACI terminal input selection
0: 4 to 20 mA
1: 0 to 10V
2: 0 to 20 mA
0
03-30
PLC analog output terminal status
Monitor the status of the PLC analog output terminals
bit 0: AFM
Read only