Operating Instructions

Summary of Parameter Settings
05 Motor Parameters
49 | 443
Pr.
Explanation
Settings
Default
04-56
PLC buffer 6
065535
0
04-57
PLC buffer 7
065535
0
04-58
PLC buffer 8
065535
0
04-59
PLC buffer 9
065535
0
04-60
PLC buffer 10
065535
0
04-61
PLC buffer 11
065535
0
04-62
PLC buffer 12
065535
0
04-63
PLC buffer 13
065535
0
04-64
PLC buffer 14
065535
0
04-65
PLC buffer 15
065535
0
04-66
PLC buffer 16
065535
0
04-67
PLC buffer 17
065535
0
04-68
PLC buffer 18
065535
0
04-69
PLC buffer 19
065535
0
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
05-00
Motor parameter
auto-tuning
0: No function
1: Dynamic test for induction motor (IM)
2: Static test for induction motor (IM)
5: Rolling auto-tuning for PM (IPM / SPM)
12: FOC sensorless inertia estimation
13: High frequency stall test for PM
0
05-01
Full-load current for induction
motor 1 (A)
10–120% of the drive’s rated current
Depending on
the model
power
05-02
Rated power for induction motor 1
(kW)
0.00655.35 kW
Depending on
the model
power
05-03
Rated speed for induction motor 1
(rpm)
0–xxxxx rpm (Depending on the motor’s number of poles)
1710 (60 Hz, 4 poles); 1410 (50 Hz, 4 poles)
Depending on
the motor’s
number of
poles
05-04
Number of poles for induction
motor 1
220
4
05-05
No-load current for induction
motor 1 (A)
0.00Pr.05-01 default
Depending on
the model
power