Operating Instructions

Summary of Parameter Settings
05 Motor Parameters
51 | 443
Pr.
Explanation
Settings
Default
05-28
Accumulated Watt-hour for a
motor (W-hour)
Read only
0.0
05-29
Accumulated Watt-hour for a
motor in low word (kW-hour)
Read only
0.0
05-30
Accumulated Watt-hour for a
motor in high word (MW-hour)
Read only
0.0
05-31
Accumulated motor operation
time (minutes)
01439
0
05-32
Accumulated motor operation
time (days)
065535
0
05-33
Induction motor (IM) or permanent
magnet synchronous AC motor
(PM) selection
0: IM (Induction motor)
1: SPM (Surface permanent magnet synchronous AC motor)
2: IPM (Interior permanent magnet synchronous AC motor)
0
05-34
Full-load current for a permanent
magnet synchronous AC motor
0–120% of the drive’s rated current
Depending on
the model
power
05-35
Rated power for a permanent
magnet synchronous AC motor
0.00655.35 kW
Depending on
the motor
power
05-36
Rated speed for a permanent
magnet synchronous AC motor
065535 rpm
2000
05-37
Number of poles for a permanent
magnet synchronous AC motor
065535
10
05-39
Stator resistance for a permanent
magnet synchronous AC motor
0.000–65.535 Ω
0.000
05-40
Permanent magnet synchronous
AC motor Ld
0.00655.35 mH
0.00
05-41
Permanent magnet synchronous
AC motor Lq
0.00655.35 mH
0.00
05-43
Ke parameter of a permanent
magnet synchronous AC motor
065535 (Unit: V / krpm)
0
05-64
Full-load current for induction
motor 3 (A)
10–120% of the drive’s rated current
Depending on
the model
power
05-65
Rated power for induction motor 3
(kW)
0.00655.35 kW
Depending on
the model
power
05-66
Rated speed for induction motor 3
(rpm)
0–xxxxx rpm (Depending on the motor’s number of poles)
1710 (60 Hz, 4 poles); 1410 (50 Hz, 4 poles)
Depending on
the motor’s
number of
poles
05-67
Number of poles for induction
motor 3
220
4
05-68
No-load current for induction
motor 3 (A)
0.00Pr.05-64 default
Depending on
the model
power
05-69
Stator resistance (Rs) for
induction motor 3
0.000–65.535 Ω
Depending on
the model
power