Operating Instructions

Summary of Parameter Settings
06 Protection Parameters (1)
52 | 443
Pr.
Explanation
Settings
Default
05-70
Full-load current for induction
motor 4 (A)
10–120% of the drive’s rated current
Depending on
the model
power
05-71
Rated power for induction motor 4
(kW)
0.00655.35 kW
Depending on
the model
power
05-72
Rated speed for induction motor 4
(rpm)
0xxxxx rpm (Depending on the motor’s number of poles)
1710 (60 Hz, 4 poles); 1410 (50 Hz, 4 poles)
Depending on
the motor’s
number of
poles
05-73
Number of poles for induction
motor 4
220
4
05-74
No-load current for induction
motor 4 (A)
0.00Pr.05-70 default
Depending on
the model
power
05-75
Stator resistance (Rs) for
induction motor 4
0.000–65.535 Ω
Depending on
the model
power
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
06-00
Low voltage level
115V/230V models: 150.0 to 220.0 Vdc
460V models: 300.0 to 440.0 Vdc
575V models: 375.0 to 550.0 Vdc
180.0
360.0
450.0
06-01
Over-voltage stall prevention
0: Disable
115V/230V models: 0.0 to 390.0 Vdc
460V models: 0.0 to 780.0 Vdc
575V models: 0.0 to 1000.0 Vdc
380.0
760.0
975.0
06-02
Selection for over-voltage stall
prevention
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
0
06-03
Over-current stall prevention
during acceleration
Normal load: 0 to 150%
(100% corresponds to the rated current of the drive)
Heavy load: 0 to 200%
(100% corresponds to the rated current of the drive)
120
180
06-04
Over-current stall prevention
during operation
Normal load: 0 to 150%
(100% corresponds to the rated current of the drive)
Heavy load: 0 to 200%
(100% corresponds to the rated current of the drive)
120
180
06-05
Acceleration/deceleration time
selection for stall prevention at
constant speed
0: By current acceleration/deceleration time
1: By the first acceleration/deceleration time
2: By the second acceleration/deceleration time
0