Operating Instructions

Summary of Parameter Settings
06 Protection Parameters (1)
53 | 443
Pr.
Explanation
Settings
Default
3: By the third acceleration/deceleration time
4: By the fourth acceleration/deceleration time
5: By Auto-acceleration/auto-deceleration
06-06
Over-torque detection selection
(motor 1)
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0
06-07
Over-torque detection level (motor
1)
10250%
(100% corresponds to the rated current of the drive)
120
06-08
Over-torque detection time (motor
1)
0.160.0 sec.
0.1
06-09
Over-torque detection selection
(motor 2)
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0
06-10
Over-torque detection level (motor
2)
10 to 250%
(100% corresponds to the rated current of the drive)
120
06-11
Over-torque detection time (motor
2)
0.1 to 60.0 sec.
0.1
06-12
Current limit
0 to 250%
(100% corresponds to the rated current of the drive)
150
06-13
Electronic thermal relay selection
1 (motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
06-14
Electronic thermal relay action
time 1 (motor 1)
30.0 to 600.0 sec.
60.0
06-15
Temperature level overheat (OH)
warning
32.0 to 212.0°F (0.0 to 110.0°C)
Depending on
the model
power
06-16
Stall prevention limit level
(Weak magnetic field current stall
prevention level)
0 to 100% (see Pr.06-03Pr.06-04)
100
06-17
Fault record 1
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during steady operation (ocn)
4: Ground fault (GFF)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
0
06-18
Fault record 2
0
06-19
Fault record 3
0
06-20
Fault record 4
0
06-21
Fault record 5
0
06-22
Fault record 6
0
Fault record 7 (Pr.14-70)
0
Fault record 8 (Pr.14-71)
0