Operating Instructions

Summary of Parameter Settings
06 Protection Parameters (1)
55 | 443
Pr.
Explanation
Settings
Default
84: Output phase loss W phase (oPL3)
87: Low frequency overload protection (oL3)
89: Rotor position detection error (roPd)
101: CANopen guarding error (CGdE)
102: CANopen heartbeat error (CHbE)
104: CANopen bus off error (CbFE)
105: CANopen index error (CidE)
106: CANopen station address error (CAdE)
107: CANopen index setting exceed limit (CFrE)
111: InrCOM time-out error (ictE)
121: Internal communication error (CP20)
123: Internal communication error (CP22)
124: Internal communication error (CP30)
126: Internal communication error (CP32)
127: Internal communication error (CP33)
128: Over-torque 3 (ot3)
129: Over-torque 4 (ot4)
134: Internal communication error (EoL3)
135: Internal communication error (EoL4)
140: oc hardware error (Hd6)
141: GFF occurs before run (b4GFF)
142: Auto-tune error 1 (AuE1)
143: Auto-tune error 2 (AuE2)
144: Auto-tune error 3 (AuE3)
06-23
Fault output option 1
065535 (see bit table for fault code)
0
06-24
Fault output option 2
065535 (see bit table for fault code)
0
06-25
Fault output option 3
065535 (see bit table for fault code)
0
06-26
Fault output option 4
065535 (see bit table for fault code)
0
06-27
Electronic thermal relay selection
2 (motor 2)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
06-28
Electronic thermal relay action
time 2 (motor 2)
30.0 to 600.0 sec.
60.0
06-29
PTC detection selection
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
0
06-30
PTC level
0.0 to 100.0%
50.0
06-31
Frequency command at
malfunction
0.00 to 599.00 Hz
Read only
06-32
Output frequency at malfunction
0.00 to 599.00 Hz
Read only
06-33
Output voltage at malfunction
0.0 to 6553.5V
Read only
06-34
DC bus voltage at malfunction
0.0 to 6553.5V
Read only
06-35
Output current at malfunction
0.00 to 655.35 Amp
Read only