Operating Instructions

Summary of Parameter Settings
06 Protection Parameters (1)
56 | 443
Pr.
Explanation
Settings
Default
06-36
IGBT temperature at malfunction
-3276.73276.7
o
C
Read only
06-38
Motor speed at malfunction
-3276732767 rpm
Read only
06-39
Torque command at malfunction
-3276732767%
Read only
06-40
Status of the multi-function
input terminal at malfunction
0000hFFFFh
Read only
06-41
Status of the multi-function
output terminal at malfunction
0000hFFFFh
Read only
06-42
Drive status at malfunction
0000hFFFFh
Read only
06-44
STO latch selection
0: STO latch
1: STO no latch
0
06-45
Output phase loss detection
action (OPHL)
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
3
06-46
Detection time for output phase
loss
0.000 to 65.535 sec.
0.500
06-47
Current detection level for output
phase loss
0.00 to 100.00%
1.00
06-48
DC brake time for output phase
loss
0.000 to 65.535 sec.
0.000
06-49
LvX auto-reset
0: Disable
1: Enable
0
06-53
Input phase loss detection action
(OrP)
0: Fault and ramp to stop
1: Fault and coast to stop
0
06-55
Derating protection
0: Constant rated current and limit carrier frequency by load current and
temperature
1: Constant carrier frequency and limit load current by setting carrier
frequency
2: Constant rated current (same as setting 0), but close current limit
0
06-56
PT100 voltage level 1
0.000 to 10.000V
5.000
06-57
PT100 voltage level 2
0.000 to 10.000V
7.000
06-58
PT100 level 1 frequency
protection
0.00 to 599.00 Hz
0.00
06-59
PT100 activation level 1
protection frequency delay time
0 to 6000 sec.
60
06-60
Software detection GFF current
level
0.0 to 6553.5%
60.0
06-61
Software detection GFF filter time
0.00 to 655.35 sec.
0.10
06-63
Operation time of fault record 1
(Days)
0 to 65535 days
Read only
06-64
Operation time of fault record 1
(Minutes)
0 to 1439 min.
Read only
06-65
Operation time of fault record 2
(Days)
065535 days
Read only