Operating Instructions

Summary of Parameter Settings
07 Special Parameters
57 | 443
Pr.
Explanation
Settings
Default
06-66
Operation time of fault record 2
(Minutes)
01439 min.
Read only
06-67
Operation time of fault record 3
(Days)
0 to 65535 days
Read only
06-68
Operation time of fault record 3
(Minutes)
0 to 1439 min.
Read only
06-69
Operation time of fault record 4
(Days)
0 to 65535 days
Read only
06-70
Operation time of fault record 4
(Minutes)
0 to 1439 min.
Read only
06-71
Low current setting level
0.0 to 100.0%
0.0
06-72
Low current detection time
0.00 to 360.00 sec.
0.00
06-73
Low current action
0: No function
1: Fault and coast to stop
2: Fault and ramp to stop by the second deceleration time
3: Warn and continue operation
0
06-80
Fire mode
0: Disable
1: Forward (counterclockwise) operation
2: Reverse (clockwise) operation
0
06-81
Operating frequency in fire mode
0.00 to 599.00 Hz
60.00
06-88
Operation times in fire mode
0 to 65535 times
Read only
06-90
Operation time of fault record 5
(days)
0 to 65535 days
Read only
06-91
Operation time of fault record 5
(minutes)
0 to 1439 min.
Read only
06-92
Operation time of fault record 6
(days)
0 to 65535 days
Read only
06-93
Operation time of fault record 6
(minutes)
0 to 1439 min.
Read only
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
07-00
Software brake chopper action
level
115V/230V models: 350.0 to 450.0 Vdc
460V models: 700.0 to 900.0 Vdc
575V models: 875.0 to 1000.0 Vdc
370.0
740.0
950.0
07-01
DC brake current level
0 to 100%
0
07-02
DC brake time at start-up
0.0 to 60.0 sec.
0.0
07-03
DC brake time at STOP
0. to 60.0 sec.
0.0