Pr.
Explanation
Settings
Default
07-04
DC brake frequency at STOP
0.00 to 599.00 Hz
0.00
07-05
Voltage increasing gain
1 to 200%
100
07-06
Restart after momentary power
loss
0: Stop operation
1: Speed tracking by the speed before the power loss
2: Speed tracking by the minimum output frequency
0
07-07
Allowed power loss duration
0.0 to 20.0 sec.
2.0
07-08
Base Block time
0.0 to 60.0 sec.
0.5
07-09
Current limit of speed tracking
20 to 200%
100
07-10
Restart after fault action
0: Stop operation
1: Speed tracking by current speed
2: Speed tracking by minimum output frequency
0
07-11
Number of times of restart after
fault
0 to 10
0
07-12
Speed tracking during start-up
0: Disable
1: Speed tracking by the maximum output frequency
2: Speed tracking by the motor frequency at start-up
3: Speed tracking by the minimum output frequency
0
07-13
dEb function selection
0: Disable
1: dEb with auto-acceleration / auto-deceleration, the drive does not
output the frequency after the power is restored.
2: dEb with auto-acceleration / auto-deceleration, the drive outputs the
frequency after the power is restored.
3: dEb low-voltage control, then the drive’s voltage increases to 350
Vdc/700 Vdc and ramps to stop after low frequency
4: dEb high-voltage control of 350 Vdc / 700 Vdc, and the drive ramps to
stop
0
07-15
Dwell time at acceleration
0.00 to 600.00 sec.
0.00
07-16
Dwell frequency at acceleration
0.00 to 599.00 Hz
0.00
07-17
Dwell time at deceleration
0.00 to 600.00 sec.
0.00
07-18
Dwell frequency at deceleration
0.00 to 599.00 Hz
0.00
07-19
Fan cooling control
0: Fan is always ON
1: Fan is OFF after the AC motor drive stops for one minute.
2: Fan is ON when the AC motor drive runs, fan is OFF when the AC
motor drive stops.
3: Fan turns ON when temperature (IGBT) reaches around 140°F
(60°C).
3
07-20
Emergency stop (EF) and force to
stop selection
0: Coast to stop
1: Stop by the first deceleration time
2: Stop by the second deceleration time
3: Stop by the third deceleration time
4: Stop by the fourth deceleration time
5: System deceleration
6: Automatic deceleration
0
07-21
Automatic energy-saving setting
0: Disable
1: Enable
0