Operating Instructions
Summary of Parameter Settings
09 Communication Parameters
62 | 443
Pr.
Explanation
Settings
Default
08-67
Master and auxiliary reverse
running cutoff frequency
0.0 to 100.0%
10.0
08-68
PID deviation limit
0.00 to 100.00%
0.00
08-69
Integral separation level
0.00 to 100.00%
0.00
08-70
Smart start-up level
0.00 to 100.00%
5.00
08-71
Smart start-up frequency
command
0.00 to 599.00 Hz
0.00
08-72
Smart start-up acceleration time
0.00–600.00 sec.
3.00
08-75
PID2 parameter switch condition
0: No switching (see Pr.08-01–Pr.08-03)
1: Auto-switch based on the output frequency
2: Auto-switch based on the deviation
0
08-76
PID2 parameter switch deviation
1
0.00 to Pr.08-77%
10.00
08-77
PID2 parameter switch deviation
2
Pr.08-76 to 100.00%
40.00
08-78
Allowed reverse running time after
start-up
0.0 to 6553.5 sec.
0.0
09 Communication Parameters
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
09-00
Communication address
1 to 254
1
09-01
COM1 transmission speed
4.8 to 115.2 Kbps
9.6
09-02
COM1 transmission fault
treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no fault, and continue operation
3
09-03
COM1 time-out detection
0.0–100.0 sec.
0.0
09-04
COM1 communication protocol
1: 7, N, 2 (ASCII)
2: 7, E, 1 (ASCII)
3: 7, O, 1 (ASCII)
4: 7, E, 2 (ASCII)
5: 7, O, 2 (ASCII)
6: 8, N, 1 (ASCII)
7: 8, N, 2 (ASCII)
8: 8, E, 1 (ASCII)
9: 8, O, 1 (ASCII)
10: 8, E, 2 (ASCII)
11: 8, O, 2 (ASCII)
1