Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
72 | 443
Descriptions of Parameter Settings
Descriptions of Parameter Settings
00 Drive Parameters
indicates the parameter can be set during operation.
Pr.
Explanation
Settings
Default
00-00
AC motor drive identity code
Read only
#.#
Pr.
Explanation
Settings
Default
00-01
AC motor drive rated current
display
Read only
#.#
● Pr.00-00 displays the AC motor drive identity code. Use the following specification table to check if Pr.00-01
setting is the rated current of the AC motor drive. Pr.00-01 corresponds to the identity code of Pr.00-00.
● The default is the rated current for heavy duty. Set Pr.00-16=0 to display the rated current for normal duty.
Models
115V Models: Single-phase
230V Models: Single-phase
Frame
A
B
C
A/B
B
C
Power (kW)
0.2
0.4
0.75
0.2
0.4
0.75
1.5
2.2
Power (HP)
0.25
0.5
1
0.25
0.5
1
2
3
Identity Code
102
103
104
302
303
304
305
306
Rated Current for
Heavy Duty
1.6
2.5
4.8
1.6
2.8
4.8
7.5
11
Rated Current for
Normal Duty
1.8
2.7
5.5
1.8
3.2
5
8.5
12.5
Models
230V Models: Three-phase
Frame
A
B
C
D
E
F
Power (kW)
0.2
0.4
0.75
1.5
2.2
3.7/4
5.5
7.5
11
15
Power (HP)
0.25
0.5
1
2
3
5
7.5
10
15
20
Identity Code
202
203
204
205
206
207
208
209
210
211
Rated Current for
Heavy Duty
1.6
2.8
4.8
7.5
11
17
25
33
49
65
Rated Current for
Normal Duty
1.8
3.2
5
8
12.5
19.5
27
36
51
69