Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
73 | 443
Models
460V Models: Three-phase
Frame
A/B
B
C
D
E
F
Power (kW)
0.4
0.75
1.5
2.2
3.7/4
5.5
7.5
11
15
18.5
22
Power (HP)
0.5
1
2
3
5
7.5
10
15
20
25
30
Identity Code
403
404
405
406
407
408
409
410
411
412
413
Rated Current for
Heavy Duty
1.5
2.7
4.2
5.5
9
13
17
25
32
38
45
Rated Current for
Normal Duty
1.8
3
4.6
6.5
10.5
15.7
20.5
28
36
41.5
49
Models
575V Models: Three-phase
Frame
A
B
C
D
Power (kW)
0.75
1.5
2.2
3.7
5.5
7.5
Power (HP)
1
2
3
5
7.5
10
Identity Code
504
505
506
507
508
509
Rated Current for
Heavy Duty
1.7
3
4.2
6.6
9.9
12.2
Rated Current for
Normal Duty
2.1
3.6
5
8
11.5
15
Pr.
Explanation
Settings
Default
00-02
Parameter reset
0: No function
1: Write protection for parameters
5: Return kWh displays to 0
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Slave index
8: Keypad does not respond
9: Reset all parameters to defaults (base frequency is 50 Hz)
10: Reset all parameters to defaults (base frequency is 60 Hz)
11: Reset all parameters to defaults with base frequency at 50 Hz (keep
the user-defined parameter values Pr.13-01Pr.13-50)
12: Reset all parameters to defaults with base frequency at 60 Hz (keep
the user-defined parameter values Pr.13-01Pr.13-50)
0