Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
81 | 443
Fig. 27:
Normal duty: overload rated output current 150% in 3 seconds. (120%, 1 minute). See Pr.00-17 for the setting for
the carrier frequency. Refer to Chapter 9 Specifications or Pr.00-01 for the rated current.
Heavy duty: overload rated output current 200% in 3 seconds. (150%,1 minute) See Pr.00-17 for the setting for the
carrier frequency. See Chapter 9 Specifications or Pr. 00-01 for the rated current.
Pr.00-01 varies with the setting value of Pr.00-16. The default value and maximum of Pr.06-03 and Pr.06-04 also
vary with the setting value of Pr.00-16.
In normal duty, the default setting of Pr.06-03 and Pr.06-04 is 120%, and the maximum is 150%.
In heavy duty, the default setting of Pr.06-03 and Pr.06-04 is 180%, and the maximum is 200%.
Pr.
Explanation
Settings
Default
00-17
Carrier frequency
Note: When Pr.00-11=5 (IMFOC
Sensorless), the maximum setting
value for Pr.00-17 Carrier
frequency is 10 kHz.
Normal load: 2–15 kHz
Heavy load: 2–15 kHz
4
4
Determines the PWM carrier frequency for the AC motor drive.
230V
460V
575V
Models
1–15 HP
[0.75–11 kW]
20–30 HP
[15–37 kW]
1–20 HP
[0.75–15 kW]
25–40 HP
[18.5–55 kW]
1–10 HP
[0.75–7.5 kW]
Settings Range
02–15 kHz
02–10 kHz
02–15 kHz
02–10 kHz
02–15 kHz
Normal Duty
Default
4 kHz
Heavy Duty
Default
4 kHz