Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
83 | 443
Pr.
Explanation
Settings
Default
00-21
Operation command source
(AUTO, REMOTE)
Note: HOA (Hand-Off-Auto)
function is valid only when you
use with MO function setting 42
and 56 or with KPC-CC01
(optional).
0: Digital keypad
1: External terminals
2: RS-485 communication input
3: CANopen communication card
5: Communication card (does not include CANopen card)
0
Determines the operation frequency source in the AUTO, REMOTE mode.
In the HOA mode, if the multi-function input terminal (MI) function setting 41 and 42 are OFF, the drive does not
receive any operation command and JOG is invalid.
Pr.
Explanation
Settings
Default
00-22
Stop method
0: Ramp to stop
1: Coast to stop
0
Determines how the motor is stopped when the drive receives the Stop command.
Fig. 29:
Ramp to stop: According to the set deceleration time, the AC motor drive decelerates to 0 Hz or the minimum
output frequency (Pr.01-07), and then stop.
Coast to stop: According to the load inertia, the AC motor drive stops output immediately, and the motor coasts to
stop.
Use “ramp to stop” for the safety of personnel or to prevent material from being wasted in applications where the
motor must stop immediately after the drive stops. You must set the deceleration time accordingly.
If idling is allowed or the load inertia is large, use “coast to stop”. For example, blowers, punching machines and
pumps.
Pr.
Explanation
Settings
Default
00-23
Motor direction control
0: Enable forward/reverse
1: Disable reverse
2: Disable forward
0
Enables the motor to run in the forward and reverse direction. You can use it to prevent a motor from running in a
direction that would cause injury or damage to the equipment, especially when only one running direction is
allowed for the motor load.