Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
87 | 443
Pr.
Explanation
Settings
Default
00-29
LOCAL / REMOTE selection
0: Standard HOA function
1: When switching between local and remote, the drive stops.
2: When switching between local and remote, the drive runs with
REMOTE settings for frequency and operating status.
3: When switching between local and remote, the drive runs with LOCAL
settings for frequency and operating status.
4: When switching between local and remote, the drive runs with LOCAL
settings when switched to Local and runs with REMOTE settings when
switched to Remote for frequency and operating status.
0
Pr.
Explanation
Settings
Default
00-30
Master frequency command
source (HAND, LOCAL)
Note: HOA (Hand-Off-Auto)
function is valid only when you
use with MO function setting 41
and 56 or with KPC-CC01
(optional).
0: Digital keypad
1: RS-485 communication input
2: External analog input (refer to Pr.03-00)
3: External UP / DOWN terminal (multi-function input terminals)
4: Pulse input without direction command (refer to Pr.10-16 without
considering direction)
6: CANopen communication card
7: Digital keypad potentiometer knob
8: Communication card (does not include CANopen card)
9: PID controller
0
Pr.
Explanation
Settings
Default
00-31
Operation command source
(HAND, LOCAL)
Note: HOA (Hand-Off-Auto)
function is valid only when you
use with MO function setting 41
and 56 or with KPC-CC01
(optional)
0: Digital keypad
1: External terminal
2: RS-485 communication input
3: CANopen communication card
5: Communication card (does not include CANopen card).
0