Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
87 | 443
Pr.
Explanation
Settings
Default
00-29
LOCAL / REMOTE selection
0: Standard HOA function
1: When switching between local and remote, the drive stops.
2: When switching between local and remote, the drive runs with
REMOTE settings for frequency and operating status.
3: When switching between local and remote, the drive runs with LOCAL
settings for frequency and operating status.
4: When switching between local and remote, the drive runs with LOCAL
settings when switched to Local and runs with REMOTE settings when
switched to Remote for frequency and operating status.
0
The default for Pr.00-29 is 0, that is, the standard HOA (Hand-Off-Auto) function. Set the AUTO and HAND
frequency and operation source with Pr.00-20, 00-21 and Pr.00-30, 00-31. The external terminal function (MI) = 56
for LOC / REM mode selection is disabled when Pr.00-29=0.
If Pr.00-29 is not set to 0, the top right corner of digital keypad KPC-CC01 (optional) displays LOC or REM. Set the
REMOTE and LOCAL frequency and operation source with Pr.00-20, 00-21 and Pr.00-30, 00-31. Set the multi-
function input terminal (MI) = 56 to set the LOC / REM selection. The AUTO key on the KPC-CC01 (optional) is the
REMOTE function; the HAND key is the LOCAL function.
If Pr.00-29 is not set to 0, the AUTO / HAND keys are disabled. In this case, the external terminal (MI) setting = 56
(local / remote selection) has the highest command priority.
Pr.
Explanation
Settings
Default
00-30
Master frequency command
source (HAND, LOCAL)
Note: HOA (Hand-Off-Auto)
function is valid only when you
use with MO function setting 41
and 56 or with KPC-CC01
(optional).
0: Digital keypad
1: RS-485 communication input
2: External analog input (refer to Pr.03-00)
3: External UP / DOWN terminal (multi-function input terminals)
4: Pulse input without direction command (refer to Pr.10-16 without
considering direction)
6: CANopen communication card
7: Digital keypad potentiometer knob
8: Communication card (does not include CANopen card)
9: PID controller
0
Determines the master frequency source in the HAND, LOCAL mode.
You can switch the HAND, LOCAL mode with the keypad KPC-CC01 (optional) or the multi-function input terminal
(MI) to set the master frequency source.
It returns to AUTO or REMOTE mode whenever you cycle the power. If you use a multi-function input terminal to
switch between HAND (LOCAL) and AUTO (REMOTE) mode, the highest priority is the multi-function input
terminal.
The pulse of Pr.00-20=4 (Pulse input without direction command) is input by PG or MI7.
Pr.
Explanation
Settings
Default
00-31
Operation command source
(HAND, LOCAL)
Note: HOA (Hand-Off-Auto)
function is valid only when you
use with MO function setting 41
and 56 or with KPC-CC01
(optional)
0: Digital keypad
1: External terminal
2: RS-485 communication input
3: CANopen communication card
5: Communication card (does not include CANopen card).
0
Determines the operation frequency source in the HAND, LOCAL mode.