Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
89 | 443
Pr.
Explanation
Settings
Default
00-49
Display filter time (keypad)
0.001–65.535 sec.
0.100
Minimizes the value fluctuation displayed by the digital keypad.
Pr.
Explanation
Settings
Default
00-50
Software version (date)
Read only
Read only
Displays the current drive software version by date.
Description Group 01
01 Basic Parameters
indicates the parameter can be set during operation.
Maximum Operation Frequency
Pr.
Explanation
Settings
Default
01-00
Maximum operation frequency
0.00–599.00 Hz
60.00 / 50.00
01-52
Maximum operation frequency of
motor 2
0.00–599.00 Hz
60.00 / 50.00
01-53
Maximum operation frequency of
motor 3
0.00–599.00 Hz
60.00 / 50.00
01-62
Maximum operation frequency of
motor 4
0.00–599.00 Hz
60.00 / 50.00
Determines the AC motor drive’s maximum operation frequency. All the AC motor drive frequency command
sources (analog inputs 0 to 10V, 4 to 20 mA, 0 to 20 mA, ±10V) are scaled to correspond to the output frequency
range.
Output Frequency
Pr.
Explanation
Settings
Default
01-01
Output frequency of motor 1
(Base frequency/Motor’s rated
frequency)
0.00–599.00 Hz
60.00 / 50.00
01-35
Output frequency of motor 2
(Base frequency / Motor’s rated
frequency)
0.00–599.00 Hz
60.00 / 50.00
01-54
Output frequency of motor 3
(Base frequency / Motor’s rated
frequency)
0.00–599.00 Hz
60.00 / 50.00
01-63
Output frequency of motor 4
(Base frequency / Motor’s rated
frequency)
0.00–599.00 Hz
60.00 / 50.00
Set this parameter according to the motor’s rated frequency on the motor nameplate. If the motor’s rated frequency
is 60 Hz, set this parameter to 60. If the motor’s rated frequency is 50 Hz, set this parameter to 50.