Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
90 | 443
Output Voltage
Pr.
Explanation
Settings
Default
01-02
Output voltage of motor 1
(Base voltage/Motor’s rated
voltage)
115V/230V models: 0.0–255.0V
460V models: 0.0–510.0V
575V models: 0.0–637.0V
220.0
440.0
575.0
01-36
Output voltage of motor 2
(Base voltage / Motor’s rated
voltage)
115V/230V models: 0.0–255.0V
460V models: 0.0–510.0V
575V models: 0.0–637.0V
220.0
440.0
575.0
01-55
Output voltage of motor 3
(Base voltage / Motor’s rated
voltage)
115V/230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
575V models: 0.0–637.0 V
220.0
440.0
575.0
01-64
Output voltage of motor 4
(Base voltage / Motor’s rated
voltage)
115V/230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
575V models: 0.0–637.0 V
220.0
440.0
575.0
● Set this parameter according to the rated voltage on the motor nameplate. If the motor’s rated voltage is 220V,
set this parameter to 220.0. If the motor’s rated voltage is 200V, set this parameter to 200.0.
● There are many motor types in the market and the power system for each country is different. The economical
and convenient solution is to install an AC motor drive. Then there is no problem using the motor with different
voltage and frequency inputs, and the motor drive can improve the original motor characteristics and useful life.
Mid-point Frequency 1/ Mid-point Voltage 1
Pr.
Explanation
Settings
Default
01-03
Mid-point frequency 1 of motor 1
0.00–599.00 Hz
3.00
01-04
Mid-point voltage 1 of motor 1
115V/230V models: 0.0–240.0V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
11.0
22.0
40.0
01-37
Mid-point frequency 1 of motor 2
0.00–599.00 Hz
3.00
01-38
Mid-point voltage 1 of motor 2
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0V
575V models: 0.0–600.0V
11.0
22.0
40.0
01-56
Mid-point frequency 1 of motor 3
0.00–599.00 Hz
3.00
01-57
Mid-point voltage 1 of motor 3
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
11.0
22.0
40.0
01-65
Mid-point frequency 1 of motor 4
0.00–599.00 Hz
3.00
01-66
Mid-point voltage 1 of motor 4
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
11.0
22.0
40.0