Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
91 | 443
Mid-point Frequency 2/ Mid-point Voltage 2
Pr.
Explanation
Settings
Default
01-05
Mid-point frequency 2 of motor 1
0.00–599.00 Hz
1.50
01-06
Mid-point voltage 2 of motor 1
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
5.0
10.0
26.1
01-39
Mid-point frequency 2 of motor 2
0.00–599.00 Hz
1.50
01-40
Mid-point voltage 2 of motor 2
115V/230V models: 0.0–240.0V
460V models:0.0–480.0 V
575V models: 0.0–600.0 V
5.0
10.0
26.1
01-58
Mid-point frequency 2 of motor 3
0.00–599.00 Hz
1.50
01-59
Mid-point voltage 2 of motor 3
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
5.0
10.0
26.1
01-67
Mid-point frequency 2 of motor 4
0.00–599.00 Hz
1.50
01-68
Mid-point voltage 2 of motor 4
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
5.0
10.0
26.1
Minimum Output Frequency / Minimum Output Voltage
Pr.
Explanation
Settings
Default
01-07
Minimum output frequency of
motor 1
0.00–599.00 Hz
0.50
01-08
Minimum output voltage of motor
1
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
1.0
2.0
16.7
01-41
Minimum output frequency of
motor 2
0.00–599.00 Hz
0.50
01-42
Minimum output voltage of motor
2
115V/230V models: 0.0–240.0V
460V models: 0.0–480.0V
575V models: 0.0–600.0V
1.0
2.0
16.7
01-60
Minimum output frequency of
motor 3
0.00–599.00 Hz
0.50
01-61
Minimum output voltage of motor
3
115V/230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–600.0 V
1.0
2.0
16.7
01-69
Minimum output frequency of
motor 4
0.00–599.00 Hz
0.50
01-70
Minimum output voltage of motor
4
115V/230V models: 0.0–240.0V
460V models: 0.0–480.0V
575V models: 0.0–600.0V
1.0
2.0
16.7