Operating Instructions

Descriptions of Parameter Settings
Descriptions of Parameter Settings
96 | 443
Pr.
Explanation
Settings
Default
01-12
Acceleration time 1
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-13
Deceleration time 1
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-14
Acceleration time 2
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-15
Deceleration time 2
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-16
Acceleration time 3
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-17
Deceleration time 3
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-18
Acceleration time 4
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-19
Deceleration time 4
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-20
JOG acceleration time
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
01-21
JOG deceleration time
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.06000.0 sec.
10.00
10.0
Setting the acceleration and deceleration time too short may trigger the drive’s
protection function (Pr.06-03 Over-current Stall Prevention during Acceleration or
Pr.06-01 Over-voltage Stall Prevention), and the actual acceleration and deceleration
time are longer than this setting.
Setting the acceleration time too short may cause motor damage or trigger drive
protection due to over-current during the drive’s acceleration.
Setting the deceleration time too short may cause motor damage or trigger drive
protection due to over-current during the drive’s deceleration or over-voltage.