Operating Instructions
Descriptions of Parameter Settings
Descriptions of Parameter Settings
97 | 443
JOG Frequency
Pr.
Explanation
Settings
Default
01-22
JOG frequency
0.00–599.00 Hz
6.00
Fig. 36:
You can use both the external terminal JOG and F1 key on the optional keypad KPC-CC01 (optional) to set the
JOG function. When the JOG command is ON, the AC motor drive accelerates from 0 Hz to the JOG frequency
(Pr.01-22). When the JOG command is OFF, the AC motor drive decelerates from the JOG frequency to stop. The
JOG acceleration and deceleration time (Pr.01-20, Pr.01-21) are the time to accelerate from 0.00 Hz to the JOG
frequency (Pr.01-22). You cannot execute the JOG command when the AC motor drive is running. When the JOG
command is executing, other operation commands are invalid.
Switch Frequency
Pr.
Explanation
Settings
Default
01-23
Switch frequency between first
and fourth Accel./Decel.
0.00–599.00 Hz
0.00
This function does not require the external terminal switching function; it switches the acceleration and deceleration
time automatically according to the Pr.01-23 setting. If you set the external terminal, the external terminal has
priority over Pr.01.23.
When using this function, set the S-curve acceleration time to 0 if the fourth acceleration time is short.
If Pr.01-02=10 s, Pr. 01-18=6 s, then the acceleration time is 3 s for 0 to 40 Hz and 5 s for 40 to 80 Hz.
If Pr.01-13=8 s, Pr. 01-19=2 s, then the deceleration time is 4 s for 80 to 40 Hz and 1 s for 40 to 0 Hz.