Data Sheet for Product

Submittal Sheet SED2 NEMA 12 Variable Frequency Drives with Bypass Options
Document No. 154-066
February 11, 2008
Page 2 of 8 http://www.sbt.siemens.com/hvp/drives Siemens Industry, Inc.
Product Numbers
Your Product Number:
Example Product Number:
V V A 3 4 0 . F 5 2 0 X
Model
VV VFD Variant [See Note 1]
Series
A
Voltage
3 380 to 480 V
4 500 to 600 V
HP rating
1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5,
10., 15., 20., 25., 30., 40., 50., 60.,
75., 100, 125 [See Note 3 for these selections]
Disconnect
D
Disconnect
F
Fused Disconnect
B
Circuit Breaker
NEMA rating
5 NEMA Type 12
Contactor
2 2 Contactors
3 3 Contactors
Reactor
[See Note 4]
0 None
3 Line Reactor
L Load Reactor
Filter
X Factory Required Designator
Options
(If no option is required, leave field blank)
(3-digit No.) Standard Variant Number (3-digit factory-assigned number)
Notes:
1. VV model is not availabe in all combinations.
2. Available only with Voltage Code 3.
3. Available only with Voltage Codes 3 and 4.
4. Only a single reactor can be installed in a bypass enclosure.
If both are required, a separate enclosed reactor is required.
Example Shown:
VVA340.F520X =
VVA Conventional Bypass, 380 to 480 V, 40 hp, fused disconnect,
NEMA Type 12, 2 contactors, no reactor.
Conventional Bypass
Typical Specifications
SED2 Bypass Options shall send the motor to bypass mode based on an easily accessible door-mounted selector or based on
the drive’s programmable relay. A bypass pilot light shall provide indication of the bypass mode. The bypass mode shall
provide overload protection. Contactors shall be electrically and mechanically interlocked. An essential services mode shall
send the motor to bypass regardless of the selected mode.