Understanding the Status Bar
The status bar at the bottom of the EasyComm screen provides an overview of the drive status.
NOTE: If multiple windows of parameter sets are simultaneously open, only the
status bars of the non-active windows are continuously updated (not the
parameter windows).
Figure 27.
The following sections discuss the parts of the Status Bar:
Using Command Controls, Setpoint Field, and Actual Value Field
Using Device Status Fields
Using the Bus Address Field
Using Command Controls, Setpoint Field, and Actual Value Field
At the left side of the status bar, the green 1 (ON) and red 0 (OFF) control buttons
can command the drive on or off. To use these command functions, the drive must
be in the online mode and the drive must be parameterized so that the setpoints and
control commands are effective via the serial interface as follows:
NOTES: An application has been created to complete these changes
automatically. Use the Cnfg HAND for EasyComm application.
Changing index 000 will change the automatic mode of operation,
therefore it is recommended to change index 001 for hand mode of
operation.
Changing P0700[000] will reset digital inputs to their factory default
values.
1. Scroll to Parameter P0700[001]. Double-click anywhere in the P0700 row. A
P0700 Selection of Command Source dialog box appears. Enter 4, USS on
BOP Link and click OK.
2. Scroll to Parameter P0718. Double-click anywhere in the P0718 row. A P0718
CO/BO: Hand/Auto dialog box appears. Enter 1, Hand and click OK.