Specifying Drive Properties
1. Do one of the following:
− From the File menu, click Drive Properties.
− Click the Drive Properties icon.
The Drive Properties dialog box displays.
Figure 29.
2. Fill in the fields as follows. When you are finished, click OK.
− Unit Type – Set to SED2 Easy Drive.
− Short Type – Not selectable.
− Unit Version – Set to correspond to the drive firmware revision (parameter r0018
reads/displays the drive firmware revision).
− Technology Type – Not selectable.
− Bus Address – Typically 0, unless there are more than one drive on a network.
NOTE: Multiple drive operation is not supported for North American
operations.
− Quantity of PZD – Set to 2 for drives with Basic Operator Panels (BOP) installed or
4 for drives with Advanced Operator Panels (AOP).