NOTE: The valid limit values (minimum and maximum values) for certain parameters depend on
the maximum output of the drive (such as rated current and voltage). In offline mode,
EasyComm does not of know the maximum output of the drive. Therefore, for these
parameters, you must observe the limit values that must be maintained.
For example:
Scroll to Parameter P0700[001]. Double-click anywhere in the P0700 row. A P0700 Selection of Command
Source dialog box appears. Enter 4, USS on BOP Link and click OK.
Scroll to Parameter P0718. Double-click anywhere in the P0718 row. A P0718 CO/BO: Hand/Auto dialog box
appears.
Scroll to Parameter P1000[001]. Double-click anywhere in the P1000 row. A P1000 Selection of Frequency
Setpoint dialog box appears. Enter 4, USS on BOP Link and click OK.
Now you can start, stop, and command the SED2 using the EasyComm status bar controls.
NOTE: When done using EasyComm, change the P0700[001] setting back to 1, BOP (Keypad),
P0718 setting back to 0, Auto, and the P1000[001] setting back to 1, MOP Setpoint.
Creating New Parameter Sets
You can create a new parameter set using the following methods:
• Generating parameter sets based on the factory setting
• Generating empty parameter sets
• Generating a parameter set by comparing two existing parameter sets
• Generating a parameter set by uploading the parameters from a drive
• Copy an existing parameter set by saving it under a new name