Data Sheet for Product

Submittal Sheet
Document No. 154-044
May 9, 2011
SED2 Variable Frequency Drives
Conventional Bypass (C-Bypass)
Options
Siemens Industry, Inc.
Description
The Bypass Options are companion
packages for the family of SED2
Variable Frequency Drives.
For information on the family of SED2
VFDs, see the SED2 Variable
Frequency Drives Submittal Sheet
(154-042).
Bypass Power Features
3-Contactor: Input, Output and
Bypass
Overload protection in bypass
mode.
Step-down transformer with
fused primary and secondary.
Contactors electrically and
mechanically interlocked.
Drive test function
Complete electrical isolation of drive
Input Device
Fused disconnect
Circuit breaker
(optional)
All doors are
interlocked and
padlockable
Drive
Motor
3 Contactor Bypass
Input
Device
VF0302R2
Enclosure Options
NEMA Type 1
NEMA Type 12
Reactor Options
Line reactor mounted in bypass option enclosure.
Line reactor (in NEMA 1 enclosure) supplied
separately.
Load reactor (in NEMA 1 enclosure) supplied
separately.
Bypass Control Features
Enable Input
Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Common Remote Start/Stop
Common remote start/stop can be used in both
drive and bypass mode.
Essential Services Mode
Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
No call to stop will have an effect, including open
safety or stop commands.
Only turning the power off or opening this contact
will stop the motor.
Bypass – Door Mounted Control Devices
Drive-Off-Bypass selector
Bypass pilot light
Drive Test on/off selector