Data Sheet for Product
Table Of Contents
Submittal Sheet
Document No. 154-044
May 9, 2011
SED2 Variable Frequency Drives
Conventional Bypass (C-Bypass)
Options
Siemens Industry, Inc.
Description
The Bypass Options are companion
packages for the family of SED2
Variable Frequency Drives.
For information on the family of SED2
VFDs, see the SED2 Variable
Frequency Drives Submittal Sheet
(154-042).
Bypass Power Features
• 3-Contactor: Input, Output and
Bypass
− Overload protection in bypass
mode.
− Step-down transformer with
fused primary and secondary.
− Contactors electrically and
mechanically interlocked.
− Drive test function
− Complete electrical isolation of drive
• Input Device
− Fused disconnect
− Circuit breaker
(optional)
− All doors are
interlocked and
padlockable
Drive
Motor
3 Contactor Bypass
Input
Device
VF0302R2
• Enclosure Options
− NEMA Type 1
− NEMA Type 12
• Reactor Options
− Line reactor mounted in bypass option enclosure.
− Line reactor (in NEMA 1 enclosure) supplied
separately.
− Load reactor (in NEMA 1 enclosure) supplied
separately.
Bypass Control Features
• Enable Input
− Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
• Common Remote Start/Stop
− Common remote start/stop can be used in both
drive and bypass mode.
• Essential Services Mode
− Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
− No call to stop will have an effect, including open
safety or stop commands.
− Only turning the power off or opening this contact
will stop the motor.
Bypass – Door Mounted Control Devices
• Drive-Off-Bypass selector
• Bypass pilot light
• Drive Test on/off selector