Data Sheet for Product

Submittal Sheet SED2 Variable Frequency Drives With C-Bypass Options
Document No. 154-044
May 9, 2011
Product Numbers
Your Product Number:
Example Product Number:
V
B
A
340 .F130X
Model
VB VFD with Bypass
Series
A
Conventional Bypass
Voltage
1
208 V
2 230 to 240 V
3 380 to 480 V
4 500 to 600 V
HP rating
1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5,
10, 15, 20, 25, 30, 40, 50, 60,
75, 100, 125 [See Note 1 for these selections]
Disconnect
F
Fused Disconnect
B
Circuit Breaker
NEMA rating
1NEMA Type 1
5 NEMA Type 12 (see Note 2)
Contactor
3 3 Contactors
Reactor
[See Note 3]
0None
3 Line Reactor
Filter
X Factory Required Designator
Options
(If no option is required, leave field blank)
NOTES:
1. Available only with Voltage Codes 3 and 4.
2. Available only with Voltage Code 3.
3. Only an input line reactor can be installed with a bypass option.
Load reactors are not available for factory installation, Order a separate, enclosed load reactor.
Example Shown:
VBA340.F130X =
VBA Conventional Bypass, 480V, 40 hp, fused disconnect,
NEMA Type 1, 3 contactors, no reactor.
Typical Specifications
SED2 Bypass Options shall send the motor to bypass mode based on an easily accessible door-mounted selector or based on
the drive’s programmable relay. A bypass pilot light shall provide indication of the bypass mode. The bypass mode shall
provide overload protection. Contactors shall be electrically and mechanically interlocked. An essential services mode shall
send the motor to bypass regardless of the selected mode.
Page 2 of 9 Siemens Industry, Inc.