Installation Instructions
Document No. 129-387
Installation Instructions
October 2, 2009
Page 2 of 3 Siemens Industry, Inc.
SED2 VFD Frame Sizes D, E, and F
WARNING:
Make sure that the SED2 VFD is
de-energized (off) before you install or
remove the LON Interface Option.
For frame sizes D, E, and F, the LON Interface mounts
inside the VFD housing.
1. Remove the SED2 VFD operator panel, side
cover, and bottom cover (Figures 3).
2. Disconnect operator panel extension module
(with ribbon cable) from control module by
pushing lever above extension module upwards
and simultaneously pulling extension module from
the upper sides and rocking it downward.
NOTE: Do not disconnect the ribbon cable.
3. Install the LON
Interface on the control module
(Figure 4) by inserting two bottom guides into
appropriate slots at the sides of the control
module and pushing the upper section inward
until the locking mechanism latches.
4. Install the operator panel extension module on
LON
Interface (Figure 4) by inserting two bottom
guides into appropriate slots at the sides of the
LON
Interface and pushing the upper section
inward until the locking mechanism latches.
5. Route the network cable (without connector)
through a suitable cable opening to the LON
Interface (Figure 4).
6. Terminate the end of network cable with a single,
two-pin, female L
ONWorks FTT-10A connector.
7. Attach the network cable FTT-10A connector to
connector at bottom of LON
Interface (Figure 2
and 4).
8. Reinstall the bottom cover, side cover, and the
SED2 VFD operator panel.
Figure 3. Removing the Operator Panel and Side Cover
of SED2 VFD Frame Sizes D, E, F.
Figure 4. Installing LON Interface Option on SED2 VFD Frame Sizes D, E, and F.