Operating Instructions

Troubleshooting
Siemens Building Technologies, Inc. 91
Error Cause Diagnosis/Remedy
Drive
Reaction
F0002,
Overvoltage
DC link voltage (r0026)
exceeds trip level.
Overvoltage can be
caused either by the input
supply voltage being too
high or if motor is in
regenerative mode.
Regenerative mode can
be caused by fast ramp
downs or if the motor is
driven from an active
load.
Supply voltage must lie within the
limits indicated on the SED2
rating plate.
Manually commission motor
identification per P1910.
DC link voltage controller must be
enabled (P1240) and
parameterized correctly.
Ramp-down time (P1121) must
match inertia of load.
Loose wire on output.
Set P1800=6 or 8 to reduce pulse
size.
Review quick commissioning with
User Access Level P0003=3
(expert) and specify a value for
P0309, rated motor efficiency.
On systems with multiple motors,
one may be pushing the other.
System electrical disturbance
may need correction.
If the SED2 faults on F0002
(overvoltage) on a start
command, flying start may have
to be optimized. This is typically
done by reducing the values in
P1203 and P1202.
NOTE: Higher inertia requires long
ramp-down times.
Off2
F0003,
Undervoltage
Input power supply failed.
Shock load outside the
specified limits.
Supply voltage must lie within the
limits indicated on the SED2
rating plate.
Supply voltage must not be
susceptible to temporary failures
or voltage reductions outside
tolerance.
Use Ramp-up Time P1120 to
increment the ramp-up time.
Off2