Operating Instructions

Troubleshooting
Siemens Building Technologies, Inc. 93
Error Cause Diagnosis/Remedy
Drive
Reaction
F0021,
Ground fault
The ground fault occurs if
the sum of the phase
currents is higher than 5%
of the nominal SED2
current.
NOTE: This error
message occurs on SED2s
with three current sensors;
that is, for SED2s of frame
sizes D to F.
— Off2
F0022,
Power stack
fault
The fault is caused by the
following events:
(1) dc link overcurrent =
short circuit of IGBT.
(2) short circuit of dc link
chopper
(3) ground fault.
Frame sizes A to C =
(1),(2),(3).
Frame sizes D to E =
(1),(2).
Frame size F = (2).
Since all these faults are
assigned to one signal on
the power stack, it is not
possible to establish which
one actually occurred.
Check for loose output or short.
Possible drive component failure.
Off2
F0023, Fault
at SED2
output
On-phase is interrupted at
the SED2 output.
— Off2
F0024,
Rectifier
over-
temperature
Ventilation is inadequate.
Fan is inoperative.
Ambient temperature is
too high.
Fan must turn when the SED2 is
running.
Pulse frequency (P1800) must be
set to default value 4 kHz.
F0030, Fan
fault
See previous fault in log..
See previous fault in log.
Off2
F0035, Auto
Retart
Failure
The drive sees a fault and
after attempting the number
of restarts specified by
P1211, the drive still sees
the fault so F0035 occurs.
Review r0947 (last fault code) for
the root cause of the fault and
diagnose per that fault.
Off2