Operating Instructions

Troubleshooting
Siemens Building Technologies, Inc. 97
Error Cause Diagnosis/Remedy
Drive
Reaction
F0452, Belt
failure
detected
Load condition changes at
the motor indicate a belt
failure or mechanical fault.
Motor belt OK? Is the motor
obstructed or seized?
If external speed sensor is used,
check proper function. Also
check:
P0409 (pulses/sec at rated
frequency)
P2191 (belt failure speed
tolerance monitoring)
P2192 (delay time for
P2191).
For belt failure detection without
sensor, check:
P2182 (threshold frequency
f1)
P2183 (threshold frequency
f2)
P2184 (threshold frequency
f3)
P2185 (upper torque
threshold 1)
P2186 (lower torque
threshold 1)
P2187 (upper torque
threshold 2)
P2188 (lower torque
threshold 2)
P2189 (upper torque
threshold 3)
P2190 (lower torque
threshold 3)
P2192 (delay for belt failure).
Lubricate the motor if necessary.
Off2