Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
98 Siemens Building Technologies, Inc.
Warning Messages
Error Cause Diagnosis and Remedy
Drive
Reaction
A0501, Current
limit
Motor power>SED2 power.
Motor cables are too long.
Ground faults.
Check belt tension.
Motor power (P0307)
>SED2 power (P0206).
Cable length limits must
not be exceeded.
Motor cable and motor
must not have short
circuits or ground faults.
Motor parameters must
match the motor in use.
Value of stator resistance
(P0350) must be correct.
The motor must not be
obstructed or overloaded.
Check belt tension, if
applicable.
Increase ramp-up time.
Reduce boost level.
A0502,
Overvoltage
limit
Overvoltage limit is reached.
This warning may appear on
ramp-down if the DC link is
disabled (P1240 = 0).
If this warning is displayed
permanently, check the
SED2 input voltage or
extend the ramp-down time
for the SED2.
A0503,
Undervoltage
limit
Input power failed.
The input power and
consequently the DC link
voltage (r0026) are below the
defined threshold value.
Check input supply voltage.
A0504, SED2
over-
temperature
The warning level of the SED2
heat sink temperature (r0037) is
exceeded.
This results in a reduced pulse
frequency and/or a reduced
output frequency (dependent
on parameter setting in
(P0610).
The ambient temperature
must lie within the limits
specified.
The load conditions and
duty cycle must lie within
the specified conditions.
The fan must turn when
the SED2 is running.