Operating Instructions

Troubleshooting
Siemens Building Technologies, Inc. 99
Error Cause Diagnosis and Remedy
Drive
Reaction
A0505, SED2
I
2
t
Warning level exceeded. The
current supply is reduced if
parameter P0610=1.
Check that the duty cycle
lies within the limits
specified.
Motor power
(P0307)>SED2 power
(P0206).
A0506, SED2
duty cycle
Difference between the heat
sink temperature and IGBT
exceeds the warning levels.
Make sure that the load
duty cycles (temporary
overload) lie within the limits
specified.
A0511, Motor
over-
temperature I
2
t
Motor is overloaded.
Duty cycle is outside the
tolerance.
Correct overload.
Adjust duty cycle.
Re-run quick
commissioning.
Verify motor efficiency
setup via P0309 equals
motor nameplate data.
NOTE: Set P0003=3 and
P0010=1 and then advance
to P0309. Set efficiency to
motor rated efficiency, or
99. Advance to P3900=3.
A0520,
Rectifier over-
temperature
Warning level of the rectifier
heat sink temperature is
exceeded.
Ambient temperature must
lie within the limits
specified.
Load conditions and duty
cycle must lie within the
specified conditions.
Fan must turn when the
SED2 is running.
A0523, SED2
output fault
On-phase is interrupted at the
SED2 output.
— —
A0541, Motor
data
identification
enabled
Motor data identification
(P1910) selected or running.
— —
A0600, RTOS
data loss
— —