Operating Instructions

SED2 VFD Startup, Operation, and Maintenance Manual
100 Siemens Building Technologies, Inc.
Error Cause Diagnosis and Remedy
Drive
Reaction
A0910, Vdc
(max.)
controller
disabled
Vdc maximum controller
disabled as not able to keep
the DC link voltage (r0026)
within threshold limits.
Permanent supply
overvoltage.
Occurs if the motor is driven
by a load forcing the motor to
go into energy recovery
operation.
Occurs during ramp-down of
very high duty cycles.
Input voltage must lie
within specified range.
Load must be adjusted.
In some cases, brake
resistance must be
applied.
A0911, Vdc
(max.)
controller
enabled
Vdc maximum controller is
enabled.
Ramp-down times are
increased automatically to keep
the DC link voltage (r0026)
within the limits specified.
Increase ramp-down time.
A0912, Vdc
(min) controller
enabled
Vdc minimum controller
enabled if the DC link voltage
(r0026) drops below the
minimum value.
Motor kinetic energy is used
to buffer the DC link voltage
and thus slow the SED2.
Temporary supply failures do
not automatically lead to
undervoltage shutdown.
— —
A0920, Analog
input
parameters not
set properly
Analog input parameters
must not be set to identical
values, as illogical values will
result.
Index 0: Parameter settings
for output identical.
Index 1: Parameter settings
for input identical.
Index 2: Parameter settings
for input do not correspond to
analog input type.
— —